Publication 900-UM004D-EN-E - July 2010

1-2

About Communications Methods

Communications
Specifications

Note:

Highlighted

characters in the table above indicate defaults.

➊ Direct RS-232C communication is only available with the 900-TC8. However, the 900-CONVx25(B) RS232/USB

to RS485 converter can be used for 900-TC16 and 900-TC32 controllers.

➋ Communications speed, data bits, stop bits and vertical parity can each be configured independently in the

controller’s Communications Setting function group.

➌ 900-TC8, 900-TC16, and 900-TC32 Series B controllers only.
➍ The communications data length for Modbus must be 8 bits.

Transmission procedure

When the host device transmits a command frame, the 900-TCx transmits a
response frame that corresponds to the command frame. A single response
frame is returned for each command frame. The following diagram shows the
operation of the command and response frames.

Allow a wait time of at least 2 ms until the next command is sent after the host
device receives a response from the 900-TCx temperature controller.

Table 1.1

Transmission line connection➊

RS-485 : Multiple point, or RS-232C : Point to point

Communications method➊

RS-485 (2-wire, half-duplex), or RS-232C

Synchronization method

Start-stop synchronization

Baud rate

1200, 2400, 4800,

9600

, 19200, 38400, or 57600 bps

Communication code➋

ASCII

Data bits➋

7

or 8 bits

Stop bits➋

1 or

2

bits

Error detection

Parity (none,

even

or odd) BCC (block check

character)

BCC with CompoWay/F (900-TC)

CRC-16 (Cyclic Redundancy Check 16) Modbus➍

communications

Flow control

None

Interface➊

RS-485/RS-232C

Retry function

None

Communications buffer

217 bytes➌, 40 byte

Communications response wait
time

0 to 99 ms, default time: 20 ms

Host Device
900-TCx Temperature Controller

Command Frame

Command Frame

Response Frame