Communications parameters -5, Communications parameters – Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 13

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

About Communications Methods

1-5

Communications
parameters

The 900-TCx's communications specifications are set/configured in the
Communications Setting function group. These parameters are set on the
900-TCx's front panel.

The table below shows the communications parameters and their ranges.

Note: Highlighted values indicate default settings.

The communications data length for Modbus must be 8 bits.

Table 1.2 Communication Parameters and Ranges

Parameter

Displayed
Characters

Setting Range

Set Value
(

Blue highlighted

characters indicate
defaults)

Communication protocol

psel

cwf

/mod

Communications unit
number

u-no

0…99

0,

1

…99

Baud rate

bps

1.2 / 2.4 / 4.8 /
9.6 /19.2 / 38.4
/ 57.6 (kbps)

1 .2 / 2.4 / 4.8 /

9.6

/19.2/38.4/57.6 (kbps)

Communications data
length

len

7/8(bit)

7

/8 (bit)

Communications stop bit

sbit

1/2

1/

2

Communications parity

prty

None/even/odd

none/

even

/odd

Send data wait time

sdwt

0…99

0…99 ms, default time:

20

ms