Table 3.5 status 2 contents – Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 58

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

3-16

Communications Data

Table 3.5 Status 2 Contents

Bit
Position

Status ➊➋

Bit Description

0

1

Status
(lower word)

0

Spare

OFF

---

1

Spare

OFF

---

2

Spare

OFF

---

3

Spare

OFF

---

4

Spare

OFF

---

5

Spare

OFF

---

6

Spare

OFF

---

7

Spare

OFF

---

8

Spare

OFF

---

9

Spare

OFF

---

10

OC (heater overcurrent) Alarm (CT1)

OFF

ON

11

OC (heater overcurrent) Alarm (CT2)

OFF

ON

12

Control Output 1 ON/OFF Count Alarm Output

OFF

ON

13

Control Output 2 ON/OFF Count Alarm Output

OFF

ON

14

Spare

OFF

---

15

Spare

OFF

---

Status
(upper word)

16

Spare

OFF

---

17

Spare

OFF

---

18

Spare

OFF

---

19

Spare

OFF

---

20

Invert direct/ reverse operation

Not Invert

Invert

21

SP Ramp

OFF

During SP ramp

22

Spare

OFF

---

23

Spare

OFF

---

24

Spare

OFF

---

25

Spare

OFF

---

26

Spare

OFF

---

27

Spare

OFF

---

28

Spare

OFF

---

29

Spare

OFF

---

30

Spare

OFF

---

31

Spare

OFF

---

➊ “Spare” bits are always OFF.
➋ When read in setup area 1, the status of the bits will be as follows:

Overcurrent Output: Cleared

Control Output 1 ON/OFF Count Alarm: Cleared

Control Output 2 ON/OFF Count Alarm: Cleared

Work bits 1...8: last value held

SP ramp: last value held