Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 95

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

Communications Data for Modbus

5-13

➋ The logic of the Modbus variable writing function (Operation command) is not influenced.

1336

331B

Multi-SP Usage

H’00000000 (0): OFF
H’00000001 (1): ON

Advanced
Setting
Function
Group

1338

331C

HB ON/OFF

H’00000000 (0): OFF
H’00000001 (1): ON

133A

331D

MB Command Logic
Switching ➋

H’00000000 (0): OFF
H’00000001 (1): ON

133C

331E

Input Error Output

H’00000000 (0): OFF
H’00000001 (1): ON

133E

331F

Input Shift Type

H’00000000 (0): Temperature input 1-point shift
H’00000001 (1): Temperature input 2-point shift

Advanced
Setting
Function
Group

1340

3320

MV at Stop and Error Addition

H’00000000 (0): OFF
H’00000001 (1): ON

1342

3321

ST Stable Range

H’00000001…H’0000270F (0.1…999.9)

1344

3322

RT

H’00000000 (0): OFF
H’00000001 (1): ON

1346

3323

HS Alarm

H’00000000 (0): OFF
H’00000001 (1): ON

1348

3324

LBA Detection Time

H’00000000…H’0000270F (0…9999)

134A

3325

LBA Function Group

H’00000001…H’0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)

134C

3326

LBA Band

H’00000000…H’0000270F
(0.0…999.9 for TC/Pt multi-input models)
(0.00…99.99 for Analog input models)

134E

3327

Soak Time Unit

H’00000000 (0): Minutes
H’00000001 (1): Hours

1350

3328

Alarm SP Selection

H’00000000 (0): Set point during SP ramp
H’00000001 (1): Set point

1356

332B

Manual MV Limit Enable

H’00000000 (0): OFF
H’00000001 (1): ON

135A

332D

PV Rate of Change Calculation
Period

H'00000001 to H'000003E7 (1 to 999)

135C

332E

Automatic Cooling Coefficient
Adjustment

H’00000000 (0): OFF
H’00000001 (1): ON

135E

332F

Heater Overcurrent Use

H’00000000 (0): OFF
H’00000001 (1): ON

1360

3330

Heater Overcurrent Latch

H’00000000 (0): OFF
H’00000001 (1): ON

1362

3331

Heater Overcurrent Hysteresis

H'00000001 to H'000001F4 (0.1 to 50.0)

1364

3332

Control Output 1 ON/OFF Count
Alarm Set Value

H'00000000 to H'0000270F (0 to 9999)

1366

3333

Control Output 2 ON/OFF Count
Alarm Set Value

H'00000000 to H'0000270F (0 to 9999)

Table 5.10

Address

Parameter Name

Setting (Monitor) Value

Function

Group

Four-byte

mode

Two-byte

mode