Communications Data for Modbus

➊ The parameter will not be shown on the Controller display when Alarm 3 is not assigned to an output.

Table 5.9

Address

Parameter Name

Setting (Monitor) Value

Function

Group

Four-byte

mode

Two-byte

mode

0F0E

2F07

Alarm 3 Latch ➊

H'00000000 (0): OFF
H'00000001 (1): ON

Advanced
Setting

0F10

2F08

Alarm 3 Hysteresis ➊

H'00000001…H'0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)

Initial
Setting

0F18

2F0C

Standby Sequence Reset

H'00000000 (0): Condition A
H'00000001 (1): Condition B

Advanced
Setting

0F1A

2F0D

Auxiliary Output 1 Open in Alarm

H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm

0F1C

2F0E

Auxiliary Output 2 Open in Alarm

H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm

0F1E

2F0F

Auxiliary Output 3 Open in Alarm ➊

H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm

0F22

2F11

Alarm 1 ON Delay

H'00000000…H'000003E7 (0…999)

0F24

2F12

Alarm 2 ON Delay

H'00000000…H'000003E7 (0…999)

0F26

2F13

Alarm 3 ON Delay ➊

H'00000000…H'000003E7 (0…999)

0F2A

2F15

Alarm 1 OFF Delay

H'00000000…H'000003E7 (0…999)

0F2C

2F16

Alarm 2 OFF Delay

H'00000000…H'000003E7 (0…999)

0F2E

2F17

Alarm 3 OFF Delay ➊

H'00000000…H'000003E7 (0…999)

1000

3000

PV/SP Display Screen Selection

H'00000000 (0): PV/SP
H'00000001 (1): PV/SP/multi-SP
PV/SP/MV
H'00000002 (2): PV/SP/MV
PV/SP/multi-SP
H'00000003 (3): PV/SP/multi-SP
H'00000004 (4): PV/SP/MV
H'00000005 (5): PV/SP/multi-SP
PV/SP/soak time remain
H'00000006 (6): PV/SP/MV
PV/SP/soak time remain
H'00000007 (7): PV/SP/soak time remain

1002

3001

MV Display Selection

H'00000000 (0): MV (heating)
H'00000001 (1): MV (cooling)

1006

3003

Automatic Display Return Time

H'00000000 (0): OFF
H'00000001…00000063 (1…99)

1008

3004

Display Refresh Period

H'00000000 (0):OFF
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0

1010

3008

Additional PV Display

H'00000000 (0): OFF
H'00000001 (1): ON

1016

300B

MV Display

H'00000000 (0): OFF (display of manipulated variable OFF)
H'00000001 (1): ON (display of manipulated variable ON)

1018

300C

Protect Function Group Move time

H'00000001…H'0000001E (1…30)