Communications Data for Modbus

➊ The alarm function can also be used in Controllers without alarm output terminals. In this case, confirm alarm

occurrences via the status data.

Table 5.3

Address

Parameter Name

Setting (Monitor) Value

Function

Group

Four-byte

mode

Two-byte

mode

0700

2700

Cooling Coefficient

H’00000001…H’0000270F (0.01…99.99)

Adjustment

0708

2704

Dead Band

H’FFFFF831…H’0000270F
(

199.9…999.9 for TC/Pt multi-input models)

(

19.99…99.99 for Analog input models)

070A

2705

Manual Reset Value

H’00000000…H’000003E8 (0.0…100.0)

070C

2706

Hysteresis (Heating)

H’00000001…H’0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)

070E

2707

Hysteresis (Cooling)

H’00000001…H’0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)

0710

2708

Control Period (Heat)

H’00000000 (0): 0.5
H’00000001…H’00000063 (1…99)

Initial Setting

0712

2709

Control Period (Cool)

H’00000000 (0): 0.5
H’00000001…H’00000063 (1…99)

0718

270C

SP Ramp Time Unit

H’00000000 (0): EU/second
H’00000001 (1): EU/minute
H’00000001 (2): EU/hour

Advanced
Setting

071A

270D

SP Ramp Set Value

H’00000000 (0): OFF
H’00000001…H’0000270F (1…9999)

Adjustment

071E

270F

MV at Stop

Standard: FFFFFFCE…H’0000041A (

5.0…105.0)

Heating and cooling: H’FFFFFBE6…H’0000041A
(

105.0…105.0)

0722

2711

MV at PV Error

Standard: H’FFFFFFCE…H’0000041A (

5.0…105.0)

Heating and cooling: H’FFFFFBE6to H’0000041A
(

105.0…105.0)

0726

2713

MV Change Rate Parameter

H’00000000…H’000003E8 (0.0…100.0)

072C

2716

Lower-Limit Temperature Input Shift
Value

H’FFFFF831…H’0000270F (

199.9…999.9)

0730

2718

Upper-Limit Temperature Input Shift
Value

H’FFFFF831…H’0000270F (

199.9…999.9)

0734

271A

Heater Current 1 Value Monitor

H’00000000…H’00000226 (0.0…55.0)

Operating

0736

271B

Heater Burnout Detection 1

H’00000000…H’000001F4 (0.0…50.0)

Adjustment

0738

271C

Leakage Current Value 1 Monitor

H’0000000…H’00000226 (0.0…55.0)

Operating

073A

271D

HS Alarm 1

H’00000000…H’000001F4 (0.0…50.0)

Adjustment

0746

2723

Temperature Input Shift Value

H’FFFFF831…H’0000270F (

199.9…999.9)

0748

2724

Heater Current Value 2 Monitor

H’00000000…H’00000226 (0.0…55.0)

Operating

074A

2725

Heater Burnout 2 Detection

H’00000000…H’000001F4 (0.0…50.0)

Adjustment

074C

2726

Leakage Current Value 2 Monitor

H’00000000…H’00000226 (0.0…55.0)

Operating

074E

2727

HS Alarm 2

H’00000000…H’000001F4 (0.0…50.0)

Adjustment