Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 49

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

Communications Data

3-7

C3 (83)

0016

Event input
assignment 1 ➍

H'00000000 (0): None
H'00000001 (1): RUN/STOP
H'00000002 (2): Auto/manual switch
H'00000003 (3): Program Start ➏
H'00000004 (4): Direct/reverse operation
H'00000005 (5): None
H'00000006 (6): 100% AT execute/cancel
H'00000007 (7): 40% AT execute/cancel
H'00000008 (8): Setting change enable/disable
H'00000009 (9): Communications writing enable/disable
H'0000000A (10): Alarm latch cancel

C3 (83)

0017

Event input
assignment 2 ➎

H’00000000...H’00000000A (0...10)
Same as Event input 1 Assignment

C3 (83)

001A

Multi-SP Uses

H’00000000(0) OFF
H’00000001(1) ON

Advanced
Setting
Function
Group

C3 (83)

001B

SP ramp tim e unit

H’00000000(0) EU/second
H’00000001(1) EU/minute
H’00000002(2) EU/hour

C3 (83)

001C

SP ramp set value

H’00000000(0) OFF
H’00000001…0000270F (1…9999)

Adjust-
ment

C3 (83)

001D

Standby sequence
reset method

H’00000000(0) Condition A
H’00000001(1) Condition B

C3 (83)

001E

Auxiliary output 1
open in alarm

H’00000000(0) Close in alarm
H’00000001(1) Open in alarm

Advanced
Setting

C3 (83)

001F

Alarm 1 hysteresis

H’00000001…0000270F

(0.1…999.9 for TC/Pt multi-input models)

(0.01…99.99 for Analog input models)

Initial
Setting

C3 (83)

0020

Auxiliary output 2
open in alarm

H’00000000(0) Close in alarm
H’00000001(1) Open in alarm

Advanced
Setting

C3 (83)

0021

Alarm 2 hysteresis

H’00000001…0000270F

(0.1…999.9 for TC/Pt multi-input models)

(0.01…99.99 for Analog input models)

Initial
Setting

C3 (83)

0022

Auxiliary output 3
open in alarm➋

H’00000000(0) Close in alarm
H’00000001(1) Open in alarm

Advanced
Function
Setting

C3 (83)

0023

Alarm 3 hysteresis ➋

H’00000001…0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)

Initial
Setting

C3 (83)

0024

HB ON/OFF

H’00000000(0) OFF
H’00000001(1) ON

Advanced
Setting
Function
Group

C3 (83)

0025

Heater burnout latch

H’00000000(0) OFF
H’00000001(1) ON

C3 (83)

0026

Heater burnout
hysteresis

H’00000001…00001F4 (0.1…50.0)

C3 (83)

0027

ST stable range

H’00000001…0000270F (0.1…999.9)

C3 (83)

0028

α

H’00000000…H’00000064 (0.00…1 .00)

C3 (83)

0029

MV upper limit

Standard: MV lower limit +0.1…000041A (MV lower limit

+0.1…105.0)

Adjust-
ment

Heating and cooling: H’00000000…H’0000041A (0.0…105.0)

C3 (83)

002A

MV lower limit

Standard: H’FFFFFFCE…MV upper limit -0.1 (-5.0…MV upper

limit -0.1)

Heating and cooling: H’FFFFFBE6…H’00000000 (-105.0…0.0)

Table 3.3 Variable Type C3 (83)

Variable
Type

Address

Item (Parameter)

Set (Monitor) Value

Function
Group

The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.

The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.

Communications parameters are enabled after they have been changed by resetting the controller.

For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2

For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.

PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.

The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.

The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)

P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.

The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.