Description of operation commands and precautions – Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 37

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)

2-21

Error Occurred

Description of operation commands and precautions:

• Communications Writing

Set the Communications Writing parameter to “ON: enabled” or “OFF:
disabled” with the related information setting. The setting can be
accepted in both setup area 0 and setup area 1. An operation error will
occur, however, if enabling or disabling communications writing is set
for an event input.

• RUN/STOP

Set control to “run” or “stop” with the related information setting. The
setting can be accepted in both setup area 0 and setup area 1. An
operation error will occur, however, if RUN/STOP is set for an event
input.

• Multi-SP

Set four set points beforehand in the Adjustment group so that you can
switch to a desired set point. The setting can be accepted in both setup

Table 2.29

Response
Code

Error name

Cause

1001

Command too long

The command is too long.

1002

Command too short

The command is too short.

1100

Parameter error

Instruction code and related information are wrong.

2203

Operation error

• The Communications Writing parameter is

set to OFF (disabled). However, note that the
error is accepted regardless of the
Communications Writing parameter setting
(ON/OFF).

• The command cannot be processed. For

details, refer to Description of operating
instructions and precautions information below.

• EEPROM error

Advertising