Variable type and write start address, Bit position, Composite write to variable area -13 – Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 29: Composite write to variable area

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)

2-13

Error occurred

Composite Write to Variable Area

This service reads in order the contents of specified addresses in the variable
area.

Service Request PDU

Service Response PDU

Variable Type and Write Start Address

For details on variable types and read start addresses, Refer
to Communications Data on page 2-3.

Bit Position

The 900-TCx controllers do not support bit access. Fixed to “00.”

Table 2.14

Response Code

Name

Description

0000

Normal Completion

No errors were found.

Table 2.15

Response Code

Name

Description

1002

Command too short

The command is too short.

1101

Area type error

The variable type is wrong.

110B

Response too long

The number of elements
exceeds the maximum.

1100

Parameter error

Bit position is not “00”.

2203

Operation error

EEPROM error.

Variable
type

Write
address

Variable
type

Write data

2

2

MRC SRC

0

1

1 3

0 0

2

2

4

0 0

2

2

4

Write data

Write
address

Bit
position

Bit
position

Number of elements

×

8 or 4

Number of elements

×

8 or 4

MRC SRC

0 1 1 3

2

2

4

Response
code