Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 45

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

Communications Data

3-3

C1 (81)

0003

Set Point

SP lower limit to SP upper limit

Operating

C1 (81)

0004

Alarm Value 1

H’FFFFF831…H’0000270F (-1999…9999)

C1 (81)

0005

Upper-Limit Alarm 1

H’FFFFF831…H’0000270F (-1999…9999)

C1 (81)

0006

Lower-Limit Alarm 1

H’FFFFF831…H’0000270F (-1999…9999)

C1 (81)

0007

Alarm Value 2

H’FFFFF831…H’0000270F (-1999…9999)

C1 (81)

0008

Upper-Limit Alarm 2

H’FFFFF831…H’0000270F (-1999…9999)

C1 (81)

0009

Lower-Limit Alarm 2

H’FFFFF831…H’0000270F (-1999…9999)

C1 (81)

OOOA

Alarm Value 3 ➊

H’FFFFF831…H’0000270F (-1999…9999)

C1 (81)

OOOB

Upper-Limit
Alarm 3 ➊

H’FFFFF831…H’0000270F (-1999…9999)

C1 (81)

OOOC

Lower-Limit
Alarm 3 ➊

H’FFFFF831…H’0000270F (-1999…9999)

C1 (81)

000D

Heater burnout
detection 1

H’00000000…H’000001 F4 (0.0…50.0)

Adjust
-ment

C1 (81)

000E

SP 0

SP lower limit…SP upper limit

C1 (81)

000F

SP 1

SP lower limit…SP upper limit

C1 (81)

0010

SP 2

SP lower limit…SP upper limit

C1 (81)

0011

SP 3

SP lower limit…SP upper limit

C1 (81)

0012

Temperature input
shift

H’FFFFF831…H’0000270F (-199.9…999.9)

C1 (81)

0013

Upper-limit
temperature input
shift value

H’FFFFF831…H’0000270F (-199.9…999.9)

C1 (81)

0014

Lower-limit
temperature input
shift value

H’FFFFF831…H’0000270F (-199.9…999.9)

C1 (81)

0015

Proportional band

H’00000001…H’0000270F (0.1…999.9)

C1 (81)

0016

Integral time

H’00000000…H’00000F9F (0…3999)

C1 (81)

0017

Derivative time

H’00000000…H’00000F9F (0…3999) (Range when RT is “OFF”)
H’00000000…H’0000270F (0…999.9) (Range when RT is “ON”)

C1 (81)

0018

Cooling coefficient

H’00000001…H’0000270F (0.01…99.99)

C1 (81)

0019

Dead band

H’FFFFF831…H’0000270F

(-199.9…999.9 for TC/Pt universal input models)
(-19.99...99.99 for analog input models)

C1 (81)

001A

Manual reset value

H’00000000…H’000003E8 (0.0…100.0)

C1 (81)

001B

Hysteresis (Heating)

H’00000001…H’0000270F

(0.1…999.9 for TC/Pt universal input models)
(.01...99.99 for analog input models)

C1 (81)

001C

Hysteresis (Cooling)

H’00000001…H’0000270F

(0.1…999.9 for TC/Pt universal input models)
(.01...99.99 for analog input models)

C1 (81)

001D

Heater burnout 2
detection

H’00000000…H’000001F4 (0.0…50.0)

C1 (81)

001E

HS alarm 1

H’00000000…H’000001F4 (0.0…50.0)

C1 (81)

001F

HS alarm 2

H’00000000…H’000001F4 (0.0…50.0)

C1 (81)

0020

Soak time

H’00000001…H’0000270F (1…9999)

C1 (81)

0021

Wait band

H’00000000 (0): OFF
H’00000001…H’0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)

C1 (81)

0022

MV at stop

Standard: H’FFFFFFCE…H’0000041A (

5.0…105.0)

Heating and cooling: H’FFFFFBE6…H’0000041A (

105.0…105.0)

C1 (81)

0023

MV at PV error

Standard: H’FFFFFFCE…H’0000041A (

5.0…105.0)

Heating and cooling: H’FFFFFBE6…H’0000041A (

105.0…105.0)

C1 (81)

0024

Manual manipulated
variable

Standard: H’FFFFFFCE…H’0000041A (

5.0…105.0)

Heating and cooling: H’FFFFFBE6…H’0000041A (

105.0…105.0)

Manual
Control

Table 3.2 Variable Type C1 (81)

Variable
Type

Address

Item (Parameter)

Set (Monitor) Value

Function