Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 44

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

3-2

Communications Data

➊ Not displayed on the controller’s display
➋ When the variable type is 80 (word access), the rightmost 16 bits are read.
➌ When the variable type is 80 (word access), the leftmost 16 bits are read.

Table 3.1 Variable Type C0 (80)

Variable
Type

Address

Item (Parameter)
Name

Set (monitor) Value

Function
Group

C0 (80)

0000

Process value

Temperature: Follow the specified range of the sensor.

Operation

Analog: Scaling lower limit -5%FS to scaling upper limit +5%FS

C0 (80)

0001

Status➊➋

Refer to Status Structure on page 3-13

C0 (80)

0002

Internal set point➊

SP lower limit to SP upper limit

C0 (80)

0003

Heater current 1 value
monitor

H’00000000…H’00000226 (0.0…55.0)

C0 (80)

0004

MV monitor (heating)

Standard : H’FFFFFFCE…H’0000041A (-5.0…105.0)

Heating and cooling: H’00000000…H’0000041A (0.0…105.0)

C0 (80)

0005

MV monitor (cooling)

H’00000000…H’0000041A (0.0 …105.0)

C0 (80)

0006

Heater current 2 value
monitor

H’00000000…H’00000226 (0.0…55.0)

C0 (80)

0007

Leakage current 1
monitor

H’00000000…H’00000226 (0.0…55.0)

C0 (80)

0008

Leakage current 2
monitor

H’00000000…H’00000226 (0.0…55.0)

C0 (80)

0009

Soak time remain

H’00000000…H’0000270F (0…9999)

C0 (80)

000C

Multi-SP monitor

H’00000000…H’0000270F (0…3)

C0 (80)

000E

Decimal Point
monitor

H’00000000…H’0000270F (0…3)

C0 (80)

000F

Control Output 1
ON/OFF Count
Monitor

H’00000000…H’0000270F (0…9999)

Advanced
Function

C0 (80)

0010

Control Output 2
ON/OFF Count
Monitor

H’00000000…H’0000270F (0…9999)

C0 (80)

0011

Status 2 ➊➋

Refer to Status Structure on page 3-13

Operation

C0 (80)

0012

Status ➊➌

Refer to Status Structure on page 3-13

C0 (80)

0013

Status 2 ➊➌

Refer to Status Structure on page 3-13

Table 3.2 Variable Type C1 (81)

Variable
Type

Address

Item (Parameter)

Set (Monitor) Value

Function
Group

C1 (81)

0000

Operation/adjustmen
t protection

H’00000000(0)

No restrictions in Operation and
Adjustment function groups

H’00000001(1)

Move to Adjustment function group
restricted

H’00000002(2)

Display and change of only PV" and
PV/SP parameters enabled

H’00000003(3)

Display of only PV and PV/SP parameters
enabled

Protect

C1 (81)

0001

Initial setting/
communications
protection

H’00000000(0)

Move to Initial Setting/Communications
Setting function group enabled (move to
Advanced Setting function group
displayed)

H’00000001(1)

Move to Initial Setting/Communications
Setting function group enabled (move to
Advanced Function Setting function
group not displayed)

H’00000002(2)

Move to Initial Setting/Communications
Setting function group restricted

C1 (81)

0002

Setup change
protection

H’00000000(0)

OFF (changing of setup on controller
display enabled)

H’00000001(1)

ON (changing of setup on controller
display disabled)