Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 89

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

Communications Data for Modbus

5-7

Table 5.6

Address

Parameter Name

Setting (Monitor) Value

Function Group

Four-byte mode

Two-byte mode

0D06

2D03

Linear Current Output

H'00000000 (0): 4…20 mA
H'00000001 (1): 0…20 mA

Initial Setting function
group

0D1E

2C0F

SP Upper Limit

The range of values (without decimal point) is as
follows:
Temperature: SP lower limit + 1…Input range
upper limit
Analog: SP lower limit + 1…scaling upper limit

0D20

2D10

SP Lower Limit

The range of values (without decimal point) is as
follows:
Temperature: Input range lower limit…SP upper
limit

1

Analog: Scaling lower limit…SP upper limit

1

0D22

2D11

Standard or Heating
and Cooling

H'00000000 (0): Standard
H'00000001 (1): Heating and cooling

0D24

2D12

Direct/Reverse
Operation

H'00000000 (0): Reverse operation
H'00000001 (1): Direct operation

0D28

2D14

PID/OnOff

H'00000000 (0): ON/OFF
H'00000001 (1): 2 degrees of freedom PID control

0D2A

2D15

ST

H'00000000 (0): OFF
H'00000001 (1): ON

0D2C

2D16

Program Pattern

H'00000000 (0): OFF
H'00000001 (1): STOP
H'00000002 (2): CONT

0E00

2E00

Transfer Output Type

H'00000000 (0): OFF
H'00000001 (1): Set point
H'00000002 (2): Set point during SP ramp
H'00000003 (3): PV
H'00000004 (4): MV monitor (heating)
H'00000005 (5): MV monitor (cooling)