Publication 900-UM004D-EN-E - July 2010

Communications Data

3-11

C3 (83)

0054

Soak time unit

H’00000000 (0): Minutes
H’00000001 (1): Hours

Advanced
function
setting

C3 (83)

0055

Alarm SP selection

H’00000000 (0): Set point during SP ramp
H’00000001 (1): Set point

C3 (83)

0056

Auxiliary Output 3
assignment

H’00000000…H’0000000F (0…15)
* Same settings as Auxiliary Output 1 assignments

C3 (83)

005B

Manual MV limit
enable

H’00000000 (0): OFF
H’00000001 (1): ON

C3 (83)

005D

AT calculated gain

H’00000001...H’00000064 (0.1...10.0)

C3 (83)

005E

AT Hysteresis

H’00000001...0000270F (0.1...999.9: Controllers with TC/Pt
universal input)
(0.01...9.99: Controllers with analog input)

C3 (83)

005F

Limit Cycle MV
amplitude

H’00000032...H’000001F4 (5.0...50.0)

C3 (83)

0067

PV Rate of change
calculation period

H’00000001...H’000003E7 (1...999)

C3 (83)

0068

Automatic Cooling
coefficient
adjustment

H’00000000 (0): OFF
H’00000001 (1): ON

C3 (83)

0069

Heater Overcurrent
use

H’00000000 (0): OFF
H’00000001 (1): ON

C3 (83)

006A

Heater Overcurrent
latch

H’00000000 (0): OFF
H’00000001 (1): ON

C3 (83)

006B

Heater Overcurrent
Hysteresis

H’00000001...H’000001F4 (0.1...50.0)

C3 (83)

006C

Extraction of square
root enable

H’00000000 (0): OFF
H’00000001 (1): ON

Initial set-
ting

C3 (83)

006D

PF Setting

H’00000000 (0): Not assigned.
H’00000001 (1): Run
H’00000002 (2): Stop
H’00000003 (3): RUN/STOP
H’00000004 (4): 100% AT execute
H’00000005 (5): 40% AT execute
H’00000006 (6): Alarm latch cancel
H’00000007 (7): Auto/manual switch
H’00000008 (8): Monitor/setting item

Advanced
function
setting

C3 (83)

006E

Monitor/Setting Item
1

H’00000000 (0): Disabled
H’00000001 (1): PV/SP/Multi-SP
H’00000002 (2): PV/SP/MV
H’00000003 (3): PV/SP/soak time remain
H’00000004 (4): Proportional band (P)
H’00000005 (5): Integral time (I)
H’00000006 (6): Derivative time (D)
H’00000007 (7): Alarm value 1
H’00000008 (8): Alarm value upper limit 1
H’00000009 (9): Alarm value lower limit 1
H’0000000A (10): Alarm value 2
H’0000000B (11): Alarm value upper limit 2
H’0000000C (12): Alarm value lower limit 2
H’0000000D (13): Alarm value 3
H’0000000E (14): Alarm value upper limit 3
H’0000000F (15): Alarm value lower limit 3

C3 (83)

006F

Monitor/Setting Item
2

H’00000000...H’0000000F (0 ...5)
* Same as for Monitor/Setting Item 1.

C3 (83)

0070

Monitor/Setting Item
3

H’00000000...H’0000000F (0 ...5)
* Same as for Monitor/Setting Item 1.

Table 3.3 Variable Type C3 (83)

Variable
Type

Address

Item (Parameter)

Set (Monitor) Value

Function
Group

The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.

The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.

Communications parameters are enabled after they have been changed by resetting the controller.

For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2

For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.

PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.

The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.

The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)

P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.

The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.