Read from Variable Area

This service reads from variable areas.

• Variable Type and Read Start Address

For details on Variable Types and Read Start Addresses, refer to Chapter
3, Communications Data.

• Bit position

Bit accessing is not supported on the 900-TCx. It is fixed to 00.

• Number of elements

Table 2.7

Number of Elements

Process

0000

The read operation is not performed (read data is
not appended to the service response PDU), and
processing ends in normal completion.

Double word

0001…0019 (1…25)

The read operation is carried out, and processing
ends in normal completion.

Word

0001…0032 (1…50)

Read Data

(for number of elements)

Response

Code

4

SRC

2

MRC

2

0

1

0

1

Service Response PDU:

Service Request PDU:

MRC

2

SRC

2

2

2

0

1

0

1

Variable

Type

Read Start

Address

4

Bit

Position

Number of

Elements

4

0

0

Number of elements X 8 or 4