Publication 900-UM004D-EN-E - July 2010

4-10

Modbus Communications Procedure

Figure 4.8 Response Frame

Table 4.7

Name

Description

Slave address

The value from the command frame is entered as-is.

Function code

This is the received function code.
When the function ended normally, the function code is left as-is.
When an error occurred, the hexadecimal value of H’80 is added to
the function code to indicate that the response is an error response.
Example: Received function code = H’03
Function code in response frame when an error occurred = H’83

Byte count

Contains the number of bytes of read data.

Number of
elements

Contains the number of setting data items that were read.

CRC-16

This check code is calculated with the data from the slave address
to the end of the data.
For details on the CRC-16 calculation, refer to CRC-16 Calculation
Example
on Page 4-2.

Table 4.8 Response Code

Function
Code

Error
Code

Error Name

Cause

H’83

H’02

Variable address error The read start variable address is

incorrect.
The variable area number is incorrect.

H’03

Variable data error

The number of elements exceeds the
allowed range.

H’03

Normal completion

No errors were found.

Slave

address

Function

code

Byte

count

1

1

1

2

CRC-16

0 to 212 (2

×

106)

Read data (for the

number of elements)

H'03