Communications Data for Modbus

1200

3200

PF Setting

H'00000000 (0): None
H'00000001 (1): Run
H'00000002 (2): Stop
H'00000003 (3): RUN/STOP
H'00000004 (4): 100% AT execute
H'00000005 (5): 40% AT execute
H'00000006 (6): Alarm latch cancel
H'00000007 (7): Auto/manual switch
H'00000008 (8): Monitor/setting item

Advanced
Setting
Function
Group

1204

3203

Monitor Setting Item 1

H'00000000 (0): Disabled
H'00000001 (1): PV/SP/multi-SP
H'00000002 (2): PV/SP/MV
H'00000003 (3): PV/SP/soak time remain
H'00000004 (4): Proportional band (P)
H'00000005 (5): Integral time (I)
H'00000006 (6): Derivative time (D)
H'00000007 (7): Alarm value 1
H'00000008 (8): Alarm value upper limit 1
H'00000009 (9): Alarm value lower limit 1
H'0000000A (10): Alarm value 2
H'0000000B (11): Alarm value upper limit 2
H'0000000C (12): Alarm value lower limit 2
H'0000000D (13): Alarm value 3
H'0000000E (14): Alarm value upper limit 3
H'0000000F (15): Alarm value lower limit 3

Advanced
Setting
Function
Group

1206

3203

Monitor/Setting Item 2

H’00000000 to H’0000000F (0 to 15)
* Same as for Monitor/Setting Item 1.

1208

3204

Monitor/Setting Item 3

H’00000000 to H’0000000F (0 to 15)
* Same as for Monitor/Setting Item 1.

120A

3205

Monitor/Setting Item 4

H’00000000 to H’0000000F (0 to 15)
* Same as for Monitor/Setting Item 1.

120C

3206

Monitor/Setting Item 5

H’00000000 to H’0000000F (0 to 15)
* Same as for Monitor/Setting Item 1.

130A

3305

Cold Junction Compensation
Method

H’00000000 (0): OFF
H’00000001 (1): ON

1314

330A

α

H’00000000…H’00000064 (0.00…1.00)

131E

330F

AT Calculated Gain

H’00000001…H’00000064 (0.1…10.00)

1320

3310

AT Hysteresis

H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt universal input models)
(0.01 to 9.99 for Analog input models)

1322

3311

Limit Cycle MV Amplitude

H'00000032 to H'000001F4 (5.0 to 50.0)

1328

3314

Heater Burnout Latch

H’00000000 (0): OFF
H’00000001 (1): ON

132A

3315

Heater Burnout Hysteresis

H’00000001…000001F4 (0.1…50.0)

132C

3316

HS Alarm Latch

H’00000000 (0): OFF
H’00000001 (1): ON

132E

3317

HS Alarm Hysteresis

H’00000001…000001F4 (0.1…50.0)

1334

331A

Number of Multi-SP Uses

H’00000000 (0): No multi-SP
H’00000001 (1): 2SP
H’00000002 (2): 4SP

Initial Setting
function group

Table 5.10

Address

Parameter Name

Setting (Monitor) Value

Function

Group

Four-byte

mode

Two-byte

mode