Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 85

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

Communications Data for Modbus

5-3

Table 5.2

Address

Parameter Name

Setting (Monitor) Value

Function

Group

Four

Byte

Model

Two

Byte

Model

0500

2500

Operation/Adjustment Protect

H’00000000 (0): No restrictions in Operation and Adjustment function groups
H’00000001 (1): Move to Adjustment function group is prohibited.
H’00000002 (2): Display and change of only PV and PV/SP parameters is
allowed.
H’00000003 (3): Display of only PV and PV/SP parameters is allowed.

Protect

0502

2501

Initial Setting/Communications
Protect

H’00000000 (0): Move to Initial Setting/Communications Setting function
group is allowed. (Move to Advanced Setting function group is displayed.)
H’00000001 (1): Move to Initial Setting/Communications Setting function
group is allowed. (Move to Advanced Setting function group is not
displayed.)
H’00000002 (2): Move to Initial Setting/Communications Setting function
group is prohibited.

0504

2502

Setup Change Protection

H’00000000 (0): OFF (Changing of setup on controller display is allowed.)
H’00000001 (1): ON (Changing of setup on controller display is prohibited.)

0506

2503

PF Key Protect

H’00000000 (0): OFF
H’00000001 (1): ON

0508

2504

Move to Protect function group

H’FFFFF831…H’0000270F (

1999…9999)

050A

2505

Password to Move to Protect
function group

H’FFFFF831…H’0000270F (

1999…9999)

(Can only be set. The monitor value is always H’00000000.)

050C

2506

Parameter Mask Enable

H’00000000 (0): OFF
H’00000001 (1): ON

0600

2600

Manual Manipulated Variable
(MV)

Standard: H’FFFFFFCE…H’0000041A (

5.0…105.0)

Heating and cooling: H’FFFFFBE6…H’0000041A (

105.0…105.0)

Manual
function
group

0602

2601

Set Point

SP lower limit…SP upper limit

Operation

0608

2508

Heater Current 1 Value Monitor

H’00000000…H’00000226 (0.0…55.0)

060A

2605

MV Monitor (Heating)

Standard: H’FFFFFFCE…H’0000041A (

5.0…105.0)

Heating and cooling: H’00000000…H’0000041A (0.0…105.0)

060C

2606

MV Monitor (Cooling)

H’00000000…H’0000041A (0.0…105.0)

Advertising