Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 84

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

5-2

Communications Data for Modbus

➊ Not displayed on the controller display.
➋ In 2-byte mode, the rightmost 16 bits are read.
➌ In 2-byte mode, the leftmost 16 bits are read.

Table 5.1

Address

Parameter Name

Setting (Monitor) Value

Function

Group

Four-Byte

mode

Two-Byte

mode

0000

2000

PV

Temperature: Use the specified range for each sensor.
Analog: Scaling lower limit

5% FS…Scaling upper limit + 5% FS

Operation

0002

2001

Status ➊➋

See STATUS AND STATUS 2 for details.

0004

2002

Internal Set Point ➊

SP lower limit…SP upper limit

0006

2003

Heater Current 1 Value
Monitor

H’00000000…H’00000226 (0.0…55.0)

0008

2004

MV Monitor (Heating)

Standard: H’FFFFFFCE…H’0000041A (

5.0…105.0)

Heating and cooling: H’00000000…H’0000041A (0.0…105.0)

000A

2005

MV Monitor (Cooling)

H’00000000…H’0000041A (0.0…105.0)

0106

2103

Set Point

SP lower limit…SP upper limit

0108

2104

Alarm Value 1

H’FFFFF831…H’0000270F (

1999…9999)

010A

2105

Upper-Limit Alarm 1

H’FFFFF831…H’0000270F (

1999…9999)

010C

2106

Lower-Limit Alarm 1

H’FFFFF831…H’0000270F (

1999…9999)

010E

2107

Alarm Value 2

H’FFFFF831…H’0000270F (

1999…9999)

0110

2108

Upper-Limit Alarm 2

H’FFFFF831…H’0000270F (

1999…9999)

0112

2109

Lower-Limit Alarm 2

H’FFFFF831…H’0000270F (

1999…9999)

0404

2402

PV

Temperature: Use the specified range for each sensor. Analog: Scaling lower
limit - 5% FS to Scaling Upper limit + 5% FS

0406

2403

Internal Set Point ➊

SP lower limit to SP upper limit

0408

2404

Multi-SP Monitor

H’00000000…H’00000003 (0.0…3.0)

040C

2406

Status ➊ ➋

See STATUS AND STATUS 2 for details.

040E

2407

Status ➌

See STATUS AND STATUS 2 for details.

0410

2408

Status 2 ➋

See STATUS AND STATUS 2 for details.

0412

2409

Status 2 ➌

See STATUS AND STATUS 2 for details.

0420

2410

Decimal Point Monitor

H’00000000…H’000000003 (0.0…3)

0422

2411

Control Output 1 ON/OFF
Count Monitor

H’00000000…H’00000270F (0.0…9999)

Advanced
Setting

0424

2412

Control Output 2 On/OFF
Count Monitor

H’00000000…H’00000270F (0.0…9999)