Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 47

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

Communications Data

3-5

Table 3.3 Variable Type C3 (83)

Variable
Type

Address

Item (Parameter)

Set (Monitor) Value

Function
Group

C3 (83)

0000

Input Type (TC/Pt
multi-input models)

H’00000000 (0): Pt (

200…850

°

C/

300…1500°F)

H’00000001 (1): Pt (

199.9…500.0

°

C/

199.9…900.0°F)

H’00000002 (2): Pt (0.0…100.0

°

C/0.0…210.0°F)

H’00000003 (3): JPt (

199.9…500.0

°

C/

199.9…900.0°F)

H’00000004 (4): JPt (0.0…100.0

°

C/0.0…210.0°F)

H’00000005 (5): K (

200…1300

°

C/

300…2300°F)

H’00000006 (6): K (

20.0…500.0

°

C/0.0…900.0°F)

H’00000007 (7): J (

100…850

°

C/

100…1500°F)

H’00000008 (8): J (

20.0…400.0

°

C/0.0…750.0°F)

H’00000009 (9): T (

200…400

°

C/

300…700°F)

H’0000000A (10): T (

199.9…400.0

°

C/

199.9…700.0°F)

H’0000000B (11): E (0…600

°

C/0…1100°F)

H’0000000C (12): L (

100…850

°

C/

100…1500°F)

H’0000000D (13): U (

200…400

°

C/

300…700°F)

H’0000000E (14): U (

199.9…400.0

°

C/

199.9…700.0°F)

H’0000000F (15): N (

200…1300

°

C/

300…2300°F)

H’00000010 (16): R (0…1700

°

C/0…3000°F)

H’00000011 (17): S (0…1700

°

C/0…3000°F)

H’00000012 (18): B (100…1800

°

C/300…3200°F)

H’00000013 (19): Infrared temperature sensor (K 140

°

F/60

°

C)

H’00000014 (20):Infrared temperature sensor (K 240

°

F/120

°

C)

H’00000015 (21):Infrared temperature sensor (K 280

°

F/140

°

C)

H’00000016 (22): Infrared temperature sensor (K 440

°

F/220

°

C)

H’00000017 (23): 0…50 mV
H’00000018 (24): W (0... 2300

°

C/0...3200

°

F)

H’00000019 (25): PL II (0... 1300

°

C/0...2300

°

F)

Initial
setting

Input Type (analog
input models) ➊

H’00000000 (0): 4…20 mA
H’00000001 (1): 0…20 mA
H’00000002 (2): 1…5 V
H’00000003 (3): 0…5 V
H’00000004 (4): 0…10 V

C3 (83)

0001

Scaling Upper Limit

Scaling lower limit +1…0000270F (scaling lower limit +1…9999)

C3 (83)

0002

Scaling Lower Limit

H’FFFFF831 to Scaling upper limit -1 (-1999 to scaling upper limit

-1)

C3 (83)

0003

Decimal Point
Position (TC/Pt
multi-input models)

H’00000000…H’00000001 (0…1)

Decimal Point
Position (analog input
models)

H’00000000…H’00000003 (0…3)

C3 (83)

0004

Temperature Unit

H’00000000(0):

°C

H’00000001(1):

°F

C3 (83)

0005

SP Upper Limit

The range of values (without decimal point) is as follows:
Temperature: SP lower limit + 1 to Input range upper limit
Analog: SP lower limit + 1 to Scaling upper limit

C3 (83)

0006

SP Lower Limit

The range of values (without decimal point) is as follows:
Temperature: Input range lower limit to SP upper limit - 1
Analog: Scaling lower limit to SP upper limit - 1

C3 (83)

0007

PID/ ON/OFF

H’00000000(0)

ON/OFF

H’00000001(1)

2-PID Control

C3 (83)

0008

Standard/Heating
and Cooling

H’00000000(0): Standard
H’00000001 (1)

Heating and cooling

The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.

The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.

Communications parameters are enabled after they have been changed by resetting the controller.

For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2

For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.

PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.

The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.

The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)

P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.

The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.

Advertising