Publication 900-UM004D-EN-E - July 2010

Modbus Communications Procedure

4-23

Echoback Test

Figure 4.18 Command Frame

Figure 4.19 Response Frame

➊ When the command is executed normally, the response returns the same data sent in the command.

Test Data

Enter any 2-byte hexadecimal data.

Response Code

Example Command and Response

The following example shows the command/response for an Echoback Test
command.

Table 4.18

Function Code

Error Code

Name

Description

H’88

H’03

Variable data
error

The data following the function
code was not the fixed data
(H’00, H’00).

H’08

Normal
completion

No errors were found.

Power ON

Software reset command

Setting area 0

Setting area 1

“Move-to-setting
area 1” command

Control in progress

Control stopped.

CRC-16

1

1

2

2

H'08

H'00

H'00

Test data

2 bytes

Slave

address

Function

code

Write

start address

CRC-16

1

1

2

2

H'08

H'00

H'00

Test data

2 bytes

Slave

address

Function

code

Write

start address