Publication 900-UM004D-EN-E - July 2010

Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)

2-11

Response code

Normal Completion

Error Occurred

Note: For details on AT (auto-tuning), see publication 900-UM007*.

Table 2.11

Response Code

Name

Description

0000

Normal completion

No errors were found.

Table 2.12

Response Code

Error name

Cause

1002

Command too short

The command is too short.

1101

Area type error

Wrong variable type

1103

Start address
out-of-range error

Write start address is out of range.

1104

End address
out-of-range error

The write end address (write start address
+ number of elements) exceeds the final
address of the variable area.

1003

Number of elements/
data mismatch

The number of data does not match the
number of elements.

1100

Parameter error

• Bit position is other than 00.
• Write data is out of range.

3003

Read-only data

Variable type CO was written to.

2203

Operation error

• The Communications Writing

parameter is set to OFF (disabled).

• Attempted to write to a parameter in

setup area 1 from setup area 0.

• Attempted to write to a protect

parameter from other than protect
group.

• AT (auto-tuning) was in progress. See

note.

• EEPROM error.

ATTENTION

!

Alarm function:
Even though alarms are not displayed on the
controller's display, they are all functional in
communications.