Publication 900-UM004D-EN-E - July 2010

1-6

About Communications Methods

Communications Parameter
Setup

Before you carry out communications with the 900-TCx, set up
communications unit number, baud rate and other parameters by carrying out
the following procedure. For details of operations other than communications
parameter setup, refer to the applicable 900-TCx User Manual.

Communications Parameter Setup

1. Hold down the key for at least three seconds to move from the

Operation function group to the Initial Setting function group.

2. Press the key for less than one second to move from the Initial

Setting V to the Communications Setting function group.

3. Select the parameters as shown below by pressing the

M

key.

4. Use the

D

or

U

keys to change the parameter set values.

Note: Displayed only when the Protocol Selection is CWF (900-TC)

Table 1.3 900-TCx User Manuals

Temperature Controller Model Number

User Manual

900-TC8

900-UM007*

900-TC16

900-UM007*

900-TC32

900-UM007*

c

psel

cwf

c

u-no

1

c

bps

9.6

c

len

7

c

56it

2

c

prty

eVen

c

sdwt

20

Protocol selection

Communications unit
number

Communications
baud rate

Communications data
length (See note.)

Communications stop
bits (See note.)

Communications
parity

Send data wait time