Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 48

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

3-6

Communications Data

C3 (83)

0009

ST

H’00000000(0):

OFF

H’00000001(1):

ON

Initial
Setting

C3 (83)

000A

Control Period (heat)

H’00000000 (0):

0.5

H’00000001…H’00000063 (1…99)

C3 (83)

000B

Control Period (cool)

H’00000000 (0):

0.5

H’00000001…H’00000063 (1…99)

C3 (83)

000C

Direct/Reverse
Operation

H’00000000(0) Reverse operation
H’00000001(1) Direct operation

C3 (83)

000D

Alarm 1 Type

H’00000000(0) Alarm function OFF
H’00000001(1) Upper- and lower-limit alarm
H’00000002(2) Upper-limit alarm
H’00000003(3) Lower-limit alarm
H’00000004(4) Upper- and lower-limit range alarm
H’00000005(5) Upper- and lower-limit alarm w/ standby sequence
H’00000006(6) Upper-limit alarm w/ standby sequence
H’00000007(7) Lower-limit alarm w/ standby sequence
H’00000008(8) Absolute-value upper-limit alarm
H’00000009(9) Absolute-value lower-limit alarm
H’0000000A(10) Absolute-value upper-limit alarm w/ standby

sequence

H’0000000B(11) Absolute-value lower-limit alarm w/ standby

sequence

H’0000000C(12) LBA (Loop Burnout alarm)
H’0000000D(13) PV change rate alarm

C3 (83)

000E

Alarm 2 Type

H’00000000(0) Alarm function OFF
H’00000001(1) Upper- and lower-limit alarm
H’00000002(2) Upper-limit alarm
H’00000003(3) Lower-limit alarm
H’00000004(4) Upper- and lower-limit range alarm
H’00000005(5) Upper- and lower-limit alarm w/ standby sequence
H’00000006(6) Upper-limit alarm w/ standby sequence
H’00000007(7) Lower-limit alarm w/ standby sequence
H’00000008(8) Absolute-value upper-limit alarm
H’00000009(9) Absolute-value lower-limit alarm
H’0000000A(10) Absolute-value upper-limit alarm w/ standby

sequence

H’0000000B(11) Absolute-value lower-limit alarm w/ standby

sequence

H’0000000C(12) No alarm function
H’0000000D(13) PV change rate alarm

C3 (83)

000F

Alarm 3 Type ➋

C3 (83)

0010

Communications unit
number ➌

H’00000000…H’00000063 (0…99)

Commun-
cations
setting

C3 (83)

0011

Baud rate 1➌

H’00000000(0) 1.2
H’00000001(1) 2.4
H’00000002(2) 4.8
H’00000003(3) 9.6
H’00000004(4) 19.2
H’00000005(5) 38-4
H’00000006(6) 57.6

C3 (83)

0012

Communications data
length 1➌

H’00000007(7) 7
H’00000008(8) 8

C3 (83)

0013

Communications stop
bit 1➌

H’00000001(1) 1
H’00000002(2) 2

C3 (83)

0014

Communications
parity➌

H’00000000(0) None
H’00000001(1) Even
H’00000002(2) Odd

C3 (83)

0015

Number of multi-SP
uses

H’00000000 (0): No multi-SP
H’00000001 (1): 2SP
H’00000002 (2): 4SP

Initial
Setting
Function
Group

Table 3.3 Variable Type C3 (83)

Variable
Type

Address

Item (Parameter)

Set (Monitor) Value

Function
Group

The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.

The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.

Communications parameters are enabled after they have been changed by resetting the controller.

For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2

For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.

PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.

The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.

The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)

P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.

The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.

Advertising