Publication 900-UM004D-EN-E - July 2010

Communications Data

3-9

C3 (83)

003E

Transfer output type

H’00000000 (0): OFF
H’00000001 (1): Set point
H’00000002 (2): Set point during SP ramp
H’00000003 (3): PV
H’00000004 (4): MV monitor (heating)
H’00000005 (5): MV monitor (cooling)

Initial
setting

C3 (83)

003F

Transfer output upper
limit

H’FFFFF831…H'0000270F (

1999…9999) ➑

C3 (83)

0040

Transfer output lower
limit

H’FFFFF831…H'0000270F (

1999…9999) ➑

C3 (83)

0041

Linear current output

H’00000000 (0): 4…20 mA
H’00000001 (1): 0…20 mA

C3 (83)

0042

Input shift type

H’00000000 (0): Temperature input 1-point shift
H’00000001 (1): Temperature input 2-point shift

Advanced
function
setting

C3 (83)

0043

MV at stop and error
addition

H’00000000 (0): OFF
H’00000001 (1): ON

C3 (83)

0044

Auto/manual select
addition

H’00000000 (0): OFF
H’00000001 (1): ON

C3 (83)

0045

RT

H’00000000 (0): OFF
H’00000001 (1): ON

C3 (83)

0046

HS alarm use

H’00000000 (0): OFF
H’00000001 (1): ON

C3 (83)

0047

HS alarm latch

H’00000000 (0): OFF
H’00000001 (1): ON

C3 (83)

0048

HS alarm hysteresis

H’00000001…H’000001F4 (0.1…50.0)

C3 (83)

0049

LBA detection time

H’00000000…0000270F (0…9999)

C3 (83)

004A

LBA function group

H’00000001…0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)

C3 (83)

004B

LBA band

H’00000000…0000270F
(0.0…999.9 for TC/Pt multi-input models)
(0.00…99.99 for Analog input models)

C3 (83)

004C

Protocol Setting ➌

H’00000000 (0): CompoWay/F (900-TC)
H’00000001 (1): Modbus

Communi
cations
setting

C3 (83)

004D

Send data wait
time➌

H’00000000…H’00000063 (0…99)

Table 3.3 Variable Type C3 (83)

Variable
Type

Address

Item (Parameter)

Set (Monitor) Value

Function
Group

The input type can be selected to march the connected sensor. There are two input types specifications:
Thermocouple/Resistance thermometer input and Analog input.

The parameter will not be shown on the Controller display when alarm 3 is not assigned to an output.

Communications parameters are enabled after they have been changed by resetting the controller.

For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 1
or 2

For controllers with two event inputs (events 1 and 2), this cannot be set if the number of Multi-SP uses parameter is set to 2.

PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.

The logic of CompoWay/F (900-TC) operation command code 00 (communications writing) is not affected.

The setting (monitor) range depends on the transfer output type setting. (See the setting data list for details.)

P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.

The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the Control Output 2 ON/OFF
Count Alarm turns ON.