Publication 900-UM004D-EN-E - July 2010

5-16

Communications Data for Modbus

When the control output ON time is less than 190 ms, the bit is set to “1” and the heater current is held at the last current value.

➋ “Spare” bits are always OFF.
➌ When read in setup area 1, the status of the bits will be as follows:

Alarm outputs: Cleared

Overcurrent: Last value held

HB error: Last value held

Input error: Last value held

HB and HS outputs: Cleared

Program end output: Cleared

Current hold: Last value held

Display range exceeded: Last value held

Heating and cooling outputs: Cleared

➍ NA for 900-TC8 , 900-TC16, and 900-TC32

Table 5.11 Status Details

Bit Position

Status

Bit Description

0

1

Status
(lower word)

0

Heater Overcurrent (CT1)

Not generated

Generated

1

Heater Current Hold (CT1) ➊

Update

Hold

2

A/D Converter Error

Not generated

Generated

3

HS Alarm Output (CT1)

OFF

ON

4

Spare➋

OFF

5

Display Range Exceeded

Not generated

Generated

6

Input Error

Not generated

Generated

7

Spare➋

OFF

8

Control Output (Heating)

OFF

ON

9

Control Output (Cooling)

OFF

ON

10

HB (Heater Burnout) Alarm Output (CT1)

OFF

ON

11

HB (Heater Burnout) Alarm Output (CT2)

OFF

ON

12

Alarm Output 1

OFF

ON

13

Alarm Output 2

OFF

ON

14

Alarm Output 3

OFF

ON

15

Program End Output

OFF

ON

Status
(upper word)

16

Event Input 1

OFF

ON

17

Event Input 2

OFF

ON

18

Event Input 3 ➍

OFF

ON

19

Event Input 4 ➍

OFF

ON

20

Write Mode

Backup mode

RAM write mode

21

EEPROM

RAM = EEPROM

RAM

EEPROM

22

Setup Area

Setup area 0

Setup area 1➌

23

AT Execute/Cancel

AT canceled

AT execution in progress

24

RUN/STOP

Run

Stop

25

Communications Writing

OFF (disabled)

ON (enabled)

26

Auto/Manual Switch

Automatic mode

Manual mode

27

Program Start

Reset

Start

28

Heater Overcurrent (CT2)

Not generated

Generated

29

Heater Current Hold (CT2) ➊

Update

Hold

30

Spare➋

OFF

31

HS Alarm (CT2)

OFF

ON