Wiring for 25-pin rs-232 connector on host device, Wiring for 9-pin rs-232 connector on host device, Rs-232c (applies to the 900-tc8 only) -4 – Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 12

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

1-4

About Communications Methods

RS-232C (Applies to the 900-TC8 only)

RS-232C connections are 1:1.

The total cable length is 15m max.

Use a shielded, AWG24 to AWG14 (cross-sectional area of 0.205 to
2.081 mm2) twisted-pair cable for the 900-TC8 and 900-TC16.

Use a shielded, AWG24 to AWG18 (cross-sectional area of 0.205 to
0.823 mm2) twisted-pair cable for the 900-TC32.

Wiring for 25-pin RS-232 connector on host device

Wiring for 9-pin RS-232 connector on host device

Cable Reference Diagram

900-TCxx
#24 AWG…#14 AWG
Conductor cross-section
0.205 mm to 2.081mm

2

2

No.

11

12

13

SD

RD

SG

RS-232C

900-TC8

Host Device
RS-232C : 25P

<

>

2

3

4

5

6

7

20

1

SD(TXD)

RD(RXD)

RS(RTS)

CS(CTS)

DR(DSR)

SG

ER(DTR)

FG

>

<

<

>

No.

11

12

13

SD

RD

SG

RS-232C

900-TC8

Host Device
RS-232C : 9P

<

>

3

2

7

8

6

5

4

SD(TXD)

RD(RXD)

RS(RTS)

CS(CTS)

DR(DSR)

SG

ER(DTR)

>

<

<

>

Advertising