Chapter

2

Bulletin 900 Communications Procedures
900-TCx (CompoWay/F)

Data Format

Unless otherwise indicated, numbers in this manual are expressed in
hexadecimal (with an H’ before the number: e.g., H’02). Values without the H’,
such as 00, are ASCII. The number underneath each delimiter in a frame
indicates the number of bytes.

Command Frame

BCC Calculation Example

The BCC (Block Check Character) is determined by calculating the exclusive
OR of the bytes from the node number up to ETX. The 8-bit result is written
to the BCC byte at the end of the frame.

Table 2.1

STX

This code (H’02) indicates the beginning of the communications frame
(text). Always set this character in the first byte. When STX is received
again during reception, reception is carried out again from the point
where STX was received.

Node number

• This number specifies the transmission’s destination.
• Specify the 900-TCx’s communication unit number.
• A BCD value between 00 and 99 or an ASCII value of XX can be set.
• Specify XX for a broadcast transmission. No responses will be

returned for broadcast transmissions.

• No responses will be returned from node numbers other than the

ones in the above range.

Sub-address

This is not used on the

900-TCx

. Be sure to set the sub-address to 00.

SID (service ID) This is not used on the

900-TCx

. Be sure to set the Service ID to 00.

Command text

Command text area. Refer to Structure of Command Text on page 2-5

ETX

This code (H’03) indicates the end of the text.

BCC

Block Check Character The BCC result is found by calculating the
exclusive OR of the bytes from the node number up to ETX.

STX

Node No.

1

2

2

Sub-address

0

0

0

SID

1

BCC Calculation Range

Text

Command Text

ETX

BCC

1

1

STX

Node No.

Sub-address

SID

Command Text

ETX

BCC

02H

0(30H)

0(30H) 0(30H) 0(30H) 0(30H) 0(30H) 5(35H) 0(30H) 3(33H)

03H

35H

BCC=30H

30H

30H

30H

30H

30H

35H

30H

33H

03H=35H

Calculation result 35H is set to the BCC area.