Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 91

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

Communications Data for Modbus

5-9

➊ The setting (monitor) range depends on the Transfer Output Type setting. (See the setting data list for details.)
➋ The parameter will not be shown on the Controller display when Alarm 3 is not assigned to an output.

Table 5.8

Address

Parameter Name

Setting (Monitor) Value

Function

Group

Four-byte

mode

Two-byte

mode

0E28

2E14

Transfer Output Upper Limit

H'FFFFF831…H'0000270F (

1999…9999) ➊

Initial
Setting

0E2A

2E15

Transfer Output Lower Limit

H'FFFFF831…H'0000270F (

1999…9999) ➊

0E48

2E24

Extraction of Square Root
Enable

H'00000000 (0): OFF
H'00000001 (1): ON

0F00

2F00

Alarm 1 Type

H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower-limit alarm
H'00000002 (2): Upper-limit alarm
H'00000003 (3): Lower-limit alarm
H'00000004 (4): Upper and lower-limit range alarm
H'00000005 (5): Upper and lower-limit alarm w/ standby sequence
H'00000006 (6): Upper-limit alarm w/ standby sequence
H'00000007 (7): Lower-limit alarm w/ standby sequence
H'00000008 (8): Absolute-value upper-limit alarm
H'00000009 (9): Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm w/ standby sequence
H'0000000B (11): Absolute-value lower-limit alarm w/ standby sequence
H'0000000C (12): LBA (Loop Burnout Alarm)
H'0000000D (13): PV change rate alarm

0F02

2F01

Alarm 1 Latch

H'00000000 (0): OFF
H'00000001 (1): ON

Advanced
Setting

0F04

2F02

Alarm 1 Hysteresis

H'00000001…H'0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)

Initial
Setting

0F06

2F03

Alarm 2 Type

H'00000000 (0): Alarm function OFF
H'00000001 (1): Upper and lower-limit alarm
H'00000002 (2): Upper-limit alarm
H'00000003 (3): Lower-limit alarm
H'00000004 (4): Upper and lower-limit range alarm
H'00000005 (5): Upper and lower-limit alarm w/ standby sequence
H'00000006 (6): Upper-limit alarm w/ standby sequence
H'00000007 (7): Lower-limit alarm w/ standby sequence
H'00000008 (8): Absolute-value upper-limit alarm
H'00000009 (9): Absolute-value lower-limit alarm
H'0000000A (10): Absolute-value upper-limit alarm w/standby sequence
H'0000000B (11): Absolute-value lower-limit alarm w/ standby sequence
H'0000000C (12): No alarm function
H'0000000D (13): PV change rate alarm

0F08

2F04

Alarm 2 Latch

H'00000000 (0): OFF
H'00000001 (1): ON

Advanced
Setting

0F0A

2F05

Alarm 2 Hysteresis

H'00000001…H'0000270F
(0.1…999.9 for TC/Pt multi-input models)
(0.01…99.99 for Analog input models)

Initial
Setting

0F0C

2F06

Alarm 3 Type ➋

Same settings as the Alarm 2 type.