Response frame -2, Response frame – Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual

Page 18

Advertising
background image

Publication 900-UM004D-EN-E - July 2010

2-2

Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)

Response Frame

• The end code is returned for each command frame that was addressed

to the local node.

• No response will be returned unless the frame contained all elements up

to the ETX and BCC.

• “Error Detection Priority” indicates the priority when two or more

errors occur simultaneously.

Table 2.2

End
Code

Name

Description

Error
Detection
Priority

00

Normal
completion

The command ended normally without error.

None

0F

FINS
command
error

The specified FINS command could not be executed.
The FINS response code should indicate why the
command could not be executed.

8

10

Parity error

The sum total of bits whose received data is 1 does
not match the set value of Communications Parity.

2

11

Framing
error

Stop bit is 0.

1

12

Overrun
error

An attempt was made to transfer new data when the
reception data was already full.

3

13

BCC error

The calculated BCC value is different from the
received BCC value.

5

14

Format error

• The command text contains characters other than

0 to 9, and A to F. This error is not applicable to
the echoback test. (For details, see Refer
to Echoback Test on page 2-17)

• No SID and command text. Or, no command text
• MRC/SRC not included in command text

7

16

Sub-address
error

• Illegal (unsupported) sub-address
• No sub-address, SID and command text
• Sub-address less than two characters, and no SID

and command text

6

18

Frame
length error

The received frame exceeds the fixed (supported)
number of bytes.

4

Command Text

BCC

ETX

1

1

2

2

2

End Code

Sub-address

Node No.

STX

1