Command code and related information, Response code – Rockwell Automation 900 Temperature Controller Communications Functions - Series B User Manual
Page 36

Publication 900-UM004D-EN-E - July 2010
2-20
Bulletin 900 Communications Procedures 900-TCx (CompoWay/F)
Command Code and related information
Response code
Normal Completion
Table 2.27
Command
Code
Description
Related Information
00
Communications writing
00: OFF (disabled)
01: ON (enabled)
01
RUN/STOP
00: Run
01 : Stop
02
Multi-SP
00: Set point 0
01 : Set point 1
02: Set point 2
03: Set point 3
03
AT execute/cancel
00: AT Cancel
01 : 100% AT execute
02: 40% AT execute
04
Write mode
00: Backup mode
01 : RAM write mode
05
Save RAM data
00
06
Software reset
00
07
Move to setup area 1
00
08
Move to protect function
group
00
09
Auto/manual switch
00: Automatic mode
01: Manual mode
0B
Parameter initialization
00: Initialize to defaults
0C
Alarm Latch Cancel
00: Alarm 1 latch cancel
01: Alarm 2 latch cancel
02: Alarm 3 latch cancel
03: HB alarm latch cancel
04: HS alarm latch cancel
05: OC alarm latch cancel
0F: All alarm latch cancel
0E
Invert Direct/Reverse
Operation
00: Not invert
01: Invert
11
Program start
00: Reset
01: Start
Table 2.28
Response
Code
Name
Description
0000
Normal completion
No errors were found.