Chapter 5 Monitor Remote I/O

Block Transfer Read Diagnostics

The following table lists the diagnostics for block transfer reads.

Scanner Mode Block Transfer Read Diagnostics

Counter

Description

State

Config/active/inactive.

Type

Module type from the module template.

BTR Len

Block transfer read length.

Req Update Time

Requested update time in the module configuration, in ms.

Avg Update Time

Average update time for this block transfer read, in ms. This is the average of the previous eight updates.

Min Update Time

Minimum update time for this block transfer read, in ms.

Max Update Time

Maximum update time for this block transfer read, in ms.

Update Count

Running count of updates for this block transfer read.

Ignored Reqs

Running count of update requests ignored by the block transfer module.

Prot Errors

Running count of protocol errors for this block transfer read. If this counter is incrementing, the module isn’t
responding correctly.

Request Count

Count of the number of times on successive scans this block transfer was requested. If this number is
consistently greater than 1, increase the requested update time - the module cannot respond quickly enough at
the current requested time. The counter applies to the BTR and BTW for this module.