Status indicators, Rio status indicator – remote devices status – Rockwell Automation 1756-RIO ControlLogix Remote I/O Communication Interface Module User Manual User Manual

Page 162

Advertising
background image

162

Publication 1756-UM534B-EN-P - November 2010

Appendix D Troubleshooting Display and Status Indicators

Status Indicators

The 1756-RIO module has three status indicators to indicate the state of
internal operations. The status indicators are labeled RIO, CLX, and OK.

RIO Status Indicator – Remote Devices Status

The RIO indicator displays the status of the Remote I/O network connection.
Status varies depending on the mode of the module.

Scanner Mode

In order of priority, highest first.

Module Display and Indicators

Indicator

Description

1

Module status display

2

RIO status indicator

3

CLX status indicator

4

OK status indicator

Indicator

Status

Description

RIO

Red

A frame-receive error has been received in the last
second (CRC error, abort, or time-out). Indicator stays
red for 1 second after the error occurs.

One or more racks are in error.

Flashing red/
off

At least one rack being scanned (not inhibited) is in
error. One or more racks are inhibited.

Yellow

Idle, no racks are configured.

Flashing
yellow/off

All configured racks are inhibited.

Flashing green/
off

No racks being scanned (not inhibited) are in error, but
one or more racks are inhibited.

Green

Successful communication with all configured racks,
no inhibited racks.

RIO CLX OK

44777

ADAPTER MOD

1

2

3

4

Advertising