Troubleshooting Display and Status Indicators Appendix D

Adapter Mode

In order of priority, highest first.

CLX Status Indicator – ControlBus Status

The CLX indicator displays the status of communication with the
ControlLogix processor.

Indicator

Status

Description

RIO

Red

A frame-receive error has been received in the last second
(CRC error, abort, or time-out). Indicator stays red for 1
second after the error occurs.

Flashing red/
off

One or more racks are not being scanned.

Flashing green/
off

Configuration mismatch on one or more racks.

Green

All racks are being scanned and there are no configuration
mismatches.

Indicator

Status

Description

CLX

Green

The module has successfully processed a request from the
ControlBus backplane within the last five seconds. All
required connections are open.

Flashing green/
off

Controlling Connection is open, but not all required
connections are open.

Yellow

Idle, no requests received from the backplane in the last
five seconds. No connections; empty configuration.

Flashing yellow/
off

Controlling Connection is not open.

Red

The module has returned a CIP error to a request from the
backplane within the last second. All required connections
are open.

Flashing red/off

The module has returned a CIP error within the last second.
All required connections are not open.