Chapter 3 Configure Adapter Mode
Clear Mappings
Follow these steps to clear all mappings.
1. To clear all assigned mappings, on the 56RioCfgAdpt dialog box, from
the Map menu, choose Clear All Mappings.
2. On the Clear ALL Mappings dialog box, confirm that you want to clear
the existing mappings and click Yes.
IMPORTANT
If you change mappings, make sure you clear the output table in
the ControlLogix controller to prevent inadvertently writing to
an incorrect I/O location. If you leave a value behind in the
output table, it now points to something else on the Remote I/O
network. To clear the output table, set the outputs to 0. You
must also re-import the aliases.