Configure Adapter Mode Chapter 3
3. On the I/O Module Properties, from the Module Type dialog box pull-
down menu, select the module type.
You have various choices depending on the rack type.
4. Click OK.
Active Racks
1. On the I/O Module Properties dialog box, from the Module Type
menu, select BT-MODULE. (On active racks, the only block transfer
module type is BT-MODULE.)
Module Type Selection
Mode
Description
Active
In Active mode, select BT-MODULE, and then adjust the BTR Length and BTW Length to match your ControlLogix
application. These sizes are determined by the remote I/O scanner and must match the remote I/O scanner’s
configuration.
Monitor
In Monitor mode, select the type of module that is in that location on the Remote I/O network from the pull-
down menu. If the specific module is not supported, select BT-MODULE, and adjust the sizes to match your
ControlLogix application. These sizes are determined by the remote I/O scanner and must match the remote I/O
scanner’s configuration.