Publication 1756-UM534B-EN-P - November 2010

73

Configure Adapter Mode Chapter 3

3. On the I/O Module Properties, from the Module Type dialog box pull-

down menu, select the module type.

You have various choices depending on the rack type.

4. Click OK.

Active Racks

1. On the I/O Module Properties dialog box, from the Module Type

menu, select BT-MODULE. (On active racks, the only block transfer
module type is BT-MODULE.)

Module Type Selection

Mode

Description

Active

In Active mode, select BT-MODULE, and then adjust the BTR Length and BTW Length to match your ControlLogix
application. These sizes are determined by the remote I/O scanner and must match the remote I/O scanner’s
configuration.

Monitor

In Monitor mode, select the type of module that is in that location on the Remote I/O network from the pull-
down menu. If the specific module is not supported, select BT-MODULE, and adjust the sizes to match your
ControlLogix application. These sizes are determined by the remote I/O scanner and must match the remote I/O
scanner’s configuration.