Chapter 3 Configure Adapter Mode

Adapter Mode

Configure Adapter
Summary

The following list summarizes the steps to configure the 1756-RIO module in
adapter mode.

1. Set the baud rate.

2. Autoconfigure online racks on the network. (Make sure the controller is

set to Program Mode.)

3. Set the communication path.

4. Manually add any additional racks that are not online.

5. Manually add and configure block transfer modules.

6. Map/Automap the data.

RIO Scanner
(reads inputs and
writes outputs to
scanned racks)
PLC-3, PLC-5, SLC, Etc.

C

ontr

olL

og

ix

1756-RIO in A

dapt

er

M

onit

or M

ode

1771 I/O Rack

1747 I/O Rack

Rack 1

Rack 2

Rack 3

1771 I/O Rack

Rack 4

RIO Scanner
(reads inputs and
writes ouputs to
scanned racks)
PLC-3, PLC-5, SLC, Etc.

1771 I/O Rack

1771 I/O Rack

1747 I/O Rack

Rack 1

1756-RIO

In A

dapt

er

M

ode

C

ontr

olL

og

ix

Rack 4

Rack 3

Rack 2

Two-way
communication
between the RIO
scanner and the
1756-RIO module
in adapter mode.

1756-RIO Module as an Active Rack

1756-RIO Module as a Monitored Rack

One-way
communication
between the Remote I/
O network and the
ControlLogix controller.
The RIO scanner
controls the I/O and
the ControlLogix
controller via the 1756-
RIO module in adapter
monitors all I/O data.
In monitor mode, it
monitors the I/O and
brings all input and
output data into the
ControLogix controller.

44828

44829

Universal Remote I/O Network

IMPORTANT

Configuring the 1756-RIO module as an adapter enables the RIO
module to emulate a 1771-ASB module. This allows a path for
peer-to-peer data to be exchanged between the scanner
controller and the ControlLogix owner of the RIO module over
the Remote I/O network. The adapter mode functionality does
not allow the scanner controller to directly control any 1756-I/O
in the chassis with the RIO module.