Scanner Mode I/O Map Appendix A
Block Transfer Control Write Structure
BT Write Structure Table
Offset (Words)
Bit
Description
0
0…5
BTR length (1…63 word, 0 means BT module decides)
6…7
Reserved
8
BTR.EN, block transfer read enable (manual mode only)
9
BTR.CONT (manual mode only)
BT Inhibit (automatic modes - inhibits config BTW, data BTW and data BTR)
10…15
Reserved
1
0…5
BTW length (1…63 word, 0 means BT module decides)
6…7
Reserved
8
BTW.EN, block transfer write enable (manual mode only)
9
BTW.CONT, continuous mode (manual mode only)
10…15
Reserved
2…n
0…15
BTW Data (64 integers, max)
BT Read
Offset Word 0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Write Data Container
for BTW Module
Offset Words 2…
n
Write Data Container
BT Write
Offset Word 1
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Reserved
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
BT Read Length
BT Write Length
B
T W
rit
e
Enabled
M
anual M
ode Only
C
ontinuous M
ode
M
anual M
ode Only
Reserved
Res
Res
B
T Read Enabled
M
anual M
ode Only
C
ontinuous Read /
B
T I
nhibit
44816