Monitor diagnostic counters in adapter mode – Rockwell Automation 1756-RIO ControlLogix Remote I/O Communication Interface Module User Manual User Manual

Page 120

Advertising
background image

120

Publication 1756-UM534B-EN-P - November 2010

Chapter 5 Monitor Remote I/O

Rack Diagnostic Counters

The rack diagnostic counters contain information about the operation of each
partial rack. The rows are racks, from 1…76 octal. There are four groups of
counters per rack, corresponding to the four possible starting I/O groups for
a rack.

The following table lists the rack diagnostic counters’ descriptions.

Monitor Diagnostic Counters in Adapter Mode

Follow this procedure to monitor diagnostic counters in adapter mode.

From the Monitor menu, choose Diagnostic Counters.

The 1756-RIO-ADPT DiagMon window displays. Notice that the Rack Status
Table and the Global Diag Counters are the same in adapter mode as scanner
mode diagnostics. The BT Global Update; however, shows the diagnostics for
the BTRs and BTWs in adapter mode.

Scanner Mode Rack Diagnostic Counters

Counter Description

Rx

This counter increments when the 1756-RIO module receives a packet from this rack.

Crc

This counter increments when the 1756-RIO module receives a packet with a bad CRC from this rack.

Tout

This counter increments when the 1756-RIO module sends a packet to this rack and does not receive a reply within the
time-out period.

Prtcl

This counter increments when the 1756-RIO module receives a packet from this rack that does not make sense in terms
of the protocol.

Advertising