Appendix B Adapter Mode I/O Map

Block Transfer Write Data on Monitored or Active Racks

The data mapped for block transfer writes consists of two status words
followed by up to 64 words of data on active or monitored racks. Block
transfer write data on active and monitored racks are mapped to ControlLogix
inputs.

Offset 0 bits 0…7 contain a free-running counter that increments each time a
block transfer read executes successfully.

The 1756-RIO module sets the BTR error bit; offset 0, bit 11, when an error
occurs executing a block transfer read. It clears the bit when the block transfer
read enable bit occurs.

When a block transfer read error occurs, offset 0, bit 8…10 contain an error
code.

The error codes are as follows.

Block Transfer Error Codes

Error Code

Description

0

OK

1

Time-out

0 1 2 3 4 5 6 7 8 9...

BTR

Block Transfer Write Data

1st

16-bit

Word

BTW