Chapter 2 Configure Scanner Mode

Clear Discrete Rack Data Mappings

Follow these steps to clear mappings for discrete (rack) data.

1. On the 56RioCfgScan dialog box, right-click on the rack and select Rack

Map Discretes - Clear.

2. On the Clear Rack Map dialog box, confirm that you want to clear the

existing mappings and click Yes.

IMPORTANT

All of the preceding mapping and configuration examples
currently reside only within the 56RioCfgScan software and
must be downloaded to the 1756-RIO module.

See

page 30

for download steps.