Chapter 3 Configure Adapter Mode
Manually Map Block-transfer Data
1. On the 56RioCfgAdpt dialog box, from the expanded rack list, right-
click on the module and choose BT Module Clx Map - Assign Manually.
2. On the Map BT Module… Manually dialog box, for the block transfer
read and write data, select the ControlLogix scheduled block and Data
Offset within the block.
3. Click OK to accept the mapping.
Block-transfer Data Map Destinations for Monitored and Active Racks
Field
CLX Data Type
Rack Type
Description
MonBTW
ClxInput
Monitored
Block transfer write data maps to ControlLogix controller inputs.
MonBTR
ClxInput
Monitored
Block transfer read data maps to ControlLogix controller inputs.
ActBTR
ClxOutput
Active
Block transfer read data maps to ControlLogix controller outputs (The ControlLogix
controller writes the data and the 1756-RIO module sends the data to the remote I/O
scanner.)
Block transfer write data maps to ControlLogix controller inputs.