Chapter 3 Configure Adapter Mode

Manually Map Block-transfer Data

1. On the 56RioCfgAdpt dialog box, from the expanded rack list, right-

click on the module and choose BT Module Clx Map - Assign Manually.

2. On the Map BT Module… Manually dialog box, for the block transfer

read and write data, select the ControlLogix scheduled block and Data
Offset within the block.

3. Click OK to accept the mapping.

Block-transfer Data Map Destinations for Monitored and Active Racks

Field

CLX Data Type

Rack Type

Description

MonBTW

ClxInput

Monitored

Block transfer write data maps to ControlLogix controller inputs.

MonBTR

ClxInput

Monitored

Block transfer read data maps to ControlLogix controller inputs.

ActBTR

ClxOutput

Active

Block transfer read data maps to ControlLogix controller outputs (The ControlLogix
controller writes the data and the 1756-RIO module sends the data to the remote I/O
scanner.)

Block transfer write data maps to ControlLogix controller inputs.