Chapter 3 Configure Adapter Mode
Clear Block Transfer Module Data Mappings
Follow these steps to clear the mappings for block transfer data.
1. On the 56RioCfgAdpt dialog box, from the expanded rack, right-click
on the block transfer module and choose BT Module Clx Map - Clear.
2. On the Clear BT Module Map dialog box, confirm that you want to
clear the existing mappings, and click Yes.