Monitor Remote I/O Chapter 5
Block Transfer Write Diagnostics
The following table lists the diagnostics for block transfer writes.
Scanner Mode Block Transfer Write Diagnostics
Counter
Description
Cfg Len
Length of the configuration data for this module.
Data Len
Data length.
Req Update Time
Requested update time in the module configuration, in ms.
Avg Update Time
Average update time for this block transfer write, in ms. This is the average of the previous eight updates.
Min Update Time
Minimum update time for this block transfer write, in ms.
Max Update Time
Maximum update time for this block transfer write, in ms.
Update Count
Running count of updates for this block transfer write.
Ignored Reqs
Running count of update requests ignored by the destination module for this block transfer write.
Protocol Errs
Running count of protocol errors for this block transfer write.