Reference Information

Appendix A

A-2

Table A.A
Execution Times for an SDS Instruction in the PLC-5

Number of I/O

(Step 0) Initialization

0.350 ms base +

Typical

Step Transition (No MSG)

Step Transition (with MSG)

8

0.050 ms/step

0.433 ms

0.633 ms

0.720 ms

16

0.050 ms/step

0.433 ms

0.633 ms

0.720 ms

t

32

0.050 ms/step

0.433 ms

0.633 ms

0.720 ms

Table A.B
Execution Times for an SDS Instruction in the PLC-5/250

Number of I/O

(Step 0) Initialization

0.200 ms base +

Typical

Step Transition (No MSG)

Step Transition (with MSG)

8

0.013 ms/step

0.200 ms

0.245 ms

0.270 ms

16

0.013 ms/step

0.200 ms

0.245 ms

0.270 ms

32

0.013 ms/step

0.200 ms

0.245 ms

0.270 ms

Control File Size Requirements

Tables A.C and A.D list the control file size requirements in the PLC-5
processor and the PLC-5/250 for an SDS instruction with 8, 16, and 32
I/O.

Table A.C
Control File Size Requirements for an SDS Instruction in the PLC-5

Number of I/O

Number of Words Needed for Control File

8

68

16

68

32

68

Table A.D
Control File Size Requirements for an SDS Instruction in the PLC-5/250

Number of I/O

Number of Words Needed for Control File

8

58

16

58

32

58