Entering or modifying i/o information – Rockwell Automation D64046.5.1 U MNL WIN DDMC User Manual

Page 50

Advertising
background image

Configuring SDS Instructions

Chapter 4

4-14

7.

If you have a PLC-5/250 processor, type the Message Control Block
address and press

[ENTER].

The Message Control Block address must be entered in the following
manner:

0MSGX:X

where:

0 is the Resource Manager global memory (must be set to zero)

X:X

file number (0-9999)

message control block number (0-9999)

For example, 0MSG0:0 is a valid message control block address.

The I/O Definition screen is displayed (see below).

Entering or Modifying I/O Information

The inputs and outputs you enter into the I/O Defines on the I/O Definition
screen are used by each step in the SDS instruction. You can enter logical
addresses and symbols into the I/O Definition screen.

The following figure shows the screen you see if you are modifying I/O
information. (If you are entering new information, you have additional function
key options.)

Modify I/O Definition Screen (PLC-5/250)

Smart Directed Sequencer I/O Input Defines Output Defines

Definition for Control Block 0: I:001/16 0: O:000/04

N10:0 1: I:001/15 1: O:000/01

2: I:001/14 2: O:000/02

3: IS:003/02 3:

+=Ins Cmt==+ +=Adr Cmt==+ 4: IS:003/03 4:

|DRILL | |RETURNED L| 5: 5:

|MACHINE | |S | 6: 6:

|HEAD 1 | | | 7: 7:

| | | |

| | | |

+==========+ +==========+

Operator Interface Station Addr : 77

Timebase for Step Timer : 0.01

Port Number for Message : 2

Press a key to change a parameter or <ENTER> to accept parameters.

>

Program Forces:Disabled Data:Decimal Addr:Decimal PLC–5/250 Addr 5

Station Timebas Port Documnt Modify

Address IO Addr

F1 F2 F3 F5 F7