Rockwell Automation D64046.5.1 U MNL WIN DDMC User Manual

Page 148

Advertising
background image

Reference Information

Appendix A

A-4

PLC-5 Processor

To determine the amount of program memory used per SDS instruction in
the PLC-5 processor, use the following formula:

22 words + 3 words per I/O programmed

For example, consider that we have 2 SDS instructions with 4 inputs and 2
outputs each:

2 SDS instructions (22 words + 4 inputs (3) + 2 outputs (3)) =

2 (22 + 12 + 6) =

2 (40) =

80 words of program file memory

PLC-5/250 Processor

To determine the amount of program memory used per SDS instruction in
the PLC-5/250 processor, use the formula from Table A.F depending on
your number of I/O.

Table A.F
Formulas for Determining Amount of Program File Memory for SDS
Instructions in the PLC-5/250

Number of I/O:

Formula:

8

226 words + (number of I/O points defined x 20) + x

16

258 words + (number of I/O points defined x 20) + x

32

322 words + (number of I/O points defined x 20) + x

For example, consider that we have 2 SDS instructions with 8 I/O
(4 inputs defined and 2 outputs defined):

2 SDS instructions (226 words + 4 inputs (20) + 2 outputs (20)) =

2 (226 + 80 + 40) =

2 (346) =

692 words of program file memory

Advertising