Troubleshooting the Kinetix 2000 Drive System

E18

OverSpeedFault

(Overspeed Fault)

Motor speed has exceeded 150% of maximum rated speed. The 100%
trip point is dictated by the lesser of the user velocity limits or the
motor rated base speed.

• Check cables for noise.
• Check tuning.

E19

PositionErrorFault

(Follow Error)

Position error limit was exceeded.

• Increase the feed forward gain.
• Increase following error limit or time.
• Check position loop tuning.
• Verify sizing of system.
• Verify mechanical integrity of system

within specification limits.

E20

MotFeedbackFault

(Mtr Fdbk AQB)

Motor Encoder State Error

The motor encoder encountered an
illegal transition.

• Use shielded cables with twisted pair

wires.

• Route the feedback away from

potential noise sources.

• Check the system grounds.
• Replace the motor/encoder.

E21

AuxFeedbackFault

(Aux Feedback Comm)

Communication was not established with an intelligent encoder.

Verify auxiliary encoder wiring.

E30

MotFeedbackFault

(Motor Feedback Comm)

Communication was not established with an intelligent encoder.

• Verify motor selection.
• Verify the motor supports automatic

identification.

• Verify motor encoder wiring.

E34

GroundShortFault

(Ground Fault)

Excessive ground current in
the converter was detected

Wiring error.

• Check motor power wiring.
• Check input power wiring.

Motor internal ground short.

Replace motor.

Internal malfunction.

Disconnect motor power cable from drive
and enable drive with current limit set to 0.
If fault clears, then a wiring error or motor
internal problem exists. If fault remains,
call your sales representative.

Grounded control power terminal
(applies to 230V systems only).

• Remove ground from control power

input.

• Source control power from three-phase

input power.
Refer to the Power Wiring Examples on
page 169 for more information.

• Add isolation transformer for control

power.

E35

DriveUndervoltage
Fault

(Pre-charge Fault)

Converter pre-charge cycle
failed

Low ac input voltage.

Check input ac voltage on all phases.

Internal malfunction.

Call your sales representative.

E36

DriveOvertemp
Fault

(System
Overtemperature)

Converter thermal switch
tripped

Excessive heat exists in the power
circuitry.

• Reduce acceleration rates.
• Reduce duty cycle (ON/OFF) of

commanded motion.

• Increase time permitted for motion.
• Use larger Kinetix 2000 converter.
• Check for clogged vents or defective

fan.

• Make sure cooling is not restricted by

insufficient space around the unit.

Error
Code

Fault Message
RSLogix
(HIM)

Problem or Symptom

Potential Cause

Possible Resolution