DC Common Bus Applications
213
Setting the Additional Bus 
Capacitance Parameter
In this procedure you will set the Add Bus Cap parameter using DriveExplorer 
software.
The following hardware and software tools are required to provide the 
necessary communication link between your personal computer and the 
Kinetix 2000 drive system running DriveExplorer software.
Remove SERCOS Communication
Follow these steps to remove (break) SERCOS communications.
1. Remove three-phase and control power from the Kinetix 2000 drive
system.
2. Remove one of the SERCOS fiber-optic cables.
Fiber-optic cable connections (Tx and Rx) are located on the top of each 
IAM/AM.
3. Reapply three-phase and control power.
Set the Additional Bus Capacitance Parameter
Follow these steps to set the Additional Bus Capacitance parameter.
1. Start your DriveExplorer software.
2. From the menu bar choose Explore\Connect\Local or enter Ctrl-L
from the keyboard.
Description
Catalog Numbers
Version
(1) (2)
(1)
Refer to DriveExplorer Getting Results Manual, publication 9306-GR001, for instructions.
(2)
Additional information regarding these communication and software tools is available at 
Anacanda Serial to DPI Adapter
(2) (3)
(3)
Refer to 1203-SSS (series B) FRN 3.xxx User Manual, publication 20COMM-UM001, for instructions.
RSLogix 5000
Software 9324-RLD300NE
ATTENTION
To avoid personal injury or equipment damage, at least one end of a 
SERCOS fiber-optic cable must be disconnected from the drive. This 
ensures that motion will not occur while changes are being made to 
the Add Bus Cap parameter.