Temperature fault led indicator, Shunt fault led indicator on – Rockwell Automation 2093-xxxx Kinetix 2000 Multi-axis Servo Drive User Manual User Manual
Page 141
 
Publication 2093-UM001A-EN-P — March 2007
Troubleshooting the Kinetix 2000 Drive System
141
Bus Status LED Indicator
Temperature Fault LED Indicator
Shunt Fault LED Indicator
All SM Status LED Indicators
Bus Status LED 
Indicator
Status
Potential Cause
Possible Resolution
Flashing
Normal condition when control power is applied and bus voltage is less than 
60V dc.
N/A
Steady Green
Normal condition when control power is applied and bus voltage is greater 
than 60V dc.
N/A
Off
Control power is not present.
Internal power supply failure.
Replace shunt module.
Temp Fault LED 
Indicator
Status
Potential Cause
Possible Resolution
Off
Normal condition
N/A
Steady Red
SM internal temperature 
exceeds operating 
temperature specification
Shunt module fan failed
Replace shunt module.
Shunt module temperature exceeds rating
• Allow shunt module to cool.
• Reset faults.
• Verify IAM bus regulator configuration.
External over temperature 
condition
External temperature switch is open
• Allow shunt module to cool.
• Reset faults.
• Verify IAM bus regulator configuration.
TS jumper is not present
Install jumper.
Shunt Fault LED 
Indicator
Status
Potential Cause
Possible Resolution
Off
Normal condition
N/A
Steady Red
Shorted internal or external 
shunt resistor
Mis-wired shunt jumper or other short on RC 
connector
• Correct mis-wire (shorted) condition.
• If problem persists, replace shunt module.
Mis-wired (shorted) external shunt wiring
SM Status LED 
Indicator
Status
Potential Cause
Possible Resolution
• Bus Status
• Temperature Fault
• Shunt Fault
All three SM status LED 
indicators flash 
simultaneously
Shunt module hardware failure
• Cycle power.
• If problem persists, replace shunt module.