Power wiring requirements – Rockwell Automation 2093-xxxx Kinetix 2000 Multi-axis Servo Drive User Manual User Manual
Page 73
 
Publication 2093-UM001A-EN-P — January 2007
Connecting the Kinetix 2000 Drive System
73
Power Wiring 
Requirements
Wire should be copper with 75
°C (167 °F) minimum rating. Phasing of main
ac power is arbitrary and earth ground connection is required for safe and 
proper operation. 
Segregate input power wiring and motor power cables from control wiring and 
motor feedback cables. Use shielded cable for power wiring and provide a 360° 
clamp termination.
IAM Power Wiring Requirements
IMPORTANT
The National Electrical Code and local electrical codes take 
precedence over the values and methods provided.
Module Catalog
Number Description
Connects to Terminals
Recommended Wire and Size
mm
2
(AWG)
Strip 
Length
mm (in.) 
Torque 
Value
Nm (lb-in.) 
Pin Signal
IAM
2093-AC05-MPx
Control input power
CPD-1 CTRL
1
Solid H05(07) V-U: 2.5(14)
Stranded H07 V-R: 2.5(14)
Flexible H05(07) V-K: 2.5(14)
Flexible with ferrule:2.5(14)
7 (0.28)
0.5 (4.4)
CPD-2 CTRL
2
DC bus
(1)
and 
V ac input power 
IPD-1 
IPD-2 
IPD-3 
IPD-4 
IPD-5 
IPD-6 
7 (0.28)
0.5 (4.4)
Contactor Enable
CED-1
CONT EN+
Solid H05(07) V-U: 1.5(16)
Stranded H07 V-R: 1.5(16)
Flexible H05(07) V-K: 1.5(16)
Flexible with ferrule:1.5(16) 
(2)
6.5 (0.26)
0.5 (4.4)
CED-2 CONT
EN-
(1)
DC common bus connections (leader IAM to follower IAM) should be kept as short as possible.
(2)
The actual gauge of the contactor enable wiring depends on the system configuration. Consult your machine builder, the NEC, and applicable local codes.
L1
L2
L3
DC+
DC-
ATTENTION
To avoid personal injury and/or equipment damage, make sure 
installation complies with specifications regarding wire types, 
conductor sizes, branch circuit protection, and disconnect devices. The 
National Electrical Code (NEC) and local codes outline provisions for 
safely installing electrical equipment.
To avoid personal injury and/or equipment damage, make sure motor 
power connectors are used for connection purposes only. Do not use 
them to turn the unit on and off.
To avoid personal injury and/or equipment damage, make sure 
shielded power cables are grounded to prevent potentially high 
voltages on the shield.